167904 FRCDM-25/4/03-G/BFQ

General specifications
Product name
Eaton Moeller series xEffect - FRCdM Type B, B+, Bfq RCCB
Part no.
FRCDM-25/4/03-G/BFQ
EAN
4015081644797
Product Length/Depth
80 millimetre
Product height
71 millimetre
Product width
70 millimetre
Product weight
0.32 kilogram
Compliances
RoHS conform
Certifications
IEC/EN 62423
IEC/EN 61008
IEC 61373
EN45545-2
ÖVE E 8601
Product Tradename
xEffect - FRCdM Type B, B+, Bfq
Product Type
RCCB
Product Sub Type
None
Delivery program
Application
Residual current circuit breaker - frequency converter-proof
Number of poles
Four-pole
Tripping time
Short time-delayed
10 ms delayed
Amperage Rating
25 A
Rated short-circuit strength
10 kA
Fault current rating
300 mA
Sensitivity type
All current sensitive - frequency converter-proof
Impulse withstand current
3 kA (8/20 μs) surge-proof
Type
FRCdM
Residual current circuit-breakers, digital
Type G/Bfq (ÖVE E 8601)
Technical Data - Electrical
Voltage rating (IEC/EN 60947-2)
240 V AC / 415 V AC
Voltage rating - min
50 V AC
Voltage rating - max
456 V AC
Rated operational voltage (Ue) - max
415 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Rated fault current - min
0.3 A
Rated fault current - max
0.3 A
Frequency rating
50 Hz / 60 Hz
Short-circuit rating
63 A (max. admissible back-up fuse)
Leakage current type
B
Rated residual making and breaking capacity
500 A
Admissible back-up fuse
63 A gG/gL
Admissible back-up fuse overload - max
25 A gG/gL
Rated short-time withstand current (Icw)
10 kA
Surge current capacity
3 kA
Test circuit range
196 V AC - 456 V AC
Pollution degree
2
Radiation resistance
Suitable for variable frequency drives (enhanced sensitivity)
Lifespan, electrical
4000 operations
Technical Data - Electrical - Dry Auxiliary Contact
Rated switching capacity (resistive load) of auxiliary contact at 30 V DC
2 A
Rated switching capacity (resistive load) of auxiliary contact at 240 V AC
0.25 A
Switching duty with resistive load of auxiliary contact - max
60 W
Switching voltage at AC of auxiliary contact - max
240 V
Switching voltage at DC of auxiliary contact - max
220 V
Switching current of auxiliary contact - max
2 A
Switching capacity of auxiliary contact - min
10 μA, 10 mV DC
Terminal capacity of auxiliary contact
0.25 mm² - 1.5 mm²
Technical Data - Mechanical
Frame
45 mm
Width in number of modular spacings
4
Built-in width (number of units)
70 mm (4 SU)
Built-in depth
70.5 mm
Mounting Method
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
DIN rail
Mounting position
As required
Degree of protection
IP20
IP20, IP40 with suitable enclosure
Status indication
White / blue
Terminals (top and bottom)
Twin-purpose terminals
Terminal capacity (solid wire)
1.5 mm² - 35 mm²
Connectable conductor cross section (solid-core) - min
1.5 mm²
Connectable conductor cross section (solid-core) - max
35 mm²
Terminal capacity (stranded cable)
16 mm² (2x)
Connectable conductor cross section (multi-wired) - min
1.5 mm²
Connectable conductor cross section (multi-wired) - max
16 mm²
Terminal capacity (cable)
M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, PZ2)
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Contact position indicator color
Red / green
Tightening torque
2 Nm - 2.4 Nm
Busbar material thickness
0.8 mm - 2 mm
Lifespan, mechanical
20000 operations
Permitted storage and transport temperature - min
-35 °C
Permitted storage and transport temperature - max
60 °C
Climatic proofing
25-55 °C / 90-95% relative humidity according to IEC 60068-2
Design verification as per IEC/EN 61439 - technical data
Rated operational current for specified heat dissipation (In)
25 A
Heat dissipation per pole, current-dependent
1.15 W
Equipment heat dissipation, current-dependent
4.6 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
4.6 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional information
Features
Additional equipment possible
Residual current circuit-breakers, digital
Fitted with:
Interlocking device
Functions
Short-time delayed tripping
Special features
Current test marks as per inscription
Dry auxiliary contact: > 100,000 electrical switching operations per minute at 2 A 30 VDC resistive load
Dry auxiliary contact: > 5 x 100,000 electrical switching operations per minute at 1 A 30 VDC resistive load
Maximum operating temperature is 60 °C in accordance with the de-rating table
Used with
Residual current circuit-breakers, digital
FRCdM
Type G/Bfq (ÖVE E 8601)

Technical data ETIM 9.0

Circuit breakers and fuses (EG000020) / Residual current circuit breaker (RCCB) (EC000003)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / Residual current circuit breaker (RCCB) (ecl@ss13-27-14-22-01 [AAB906019])
Number of poles
4
Rated voltage
415 V
Rated current
25 A
Rated fault current
0.3 A
Rated insulation voltage Ui
440 V
Rated impulse withstand voltage Uimp
4 kV
Power loss
W
Mounting method
DIN rail
Leakage current type
B
Selective protection
No
Short-time delayed tripping
Yes
Short-circuit breaking capacity (Icw)
10 kA
Surge current capacity
3 kA
Voltage type
AC
With interlocking device
Yes
Frequency
50/60 Hz
Additional equipment possible
Yes
Degree of protection (IP)
IP20
Width in number of modular spacings
4
Built-in depth
70.5 mm
Ambient temperature during operating
-25 - 60 °C
Pollution degree
2
Connectable conductor cross section multi-wired
1.5 - 16 mm²
Connectable conductor cross section solid-core
1.5 - 35 mm²
RAL-number (similar)
7035
Explosion-proof
No