General specifications
Product name
Eaton Distribution parts
Part no.
Z-NHK
EAN
4015082484347
Product Length/Depth
80 millimetre
Product height
75 millimetre
Product width
8.8 millimetre
Product weight
0.045 kilogram
Compliances
RoHS conform
Certifications
CSA-C22.2 No. 5-09
CSA (Class No. 1437-01)
CSA (File No. 204453)
UL (File No. E257181)
UL 489
IEC/EN 60898
CE marking
UL (Category Control Number DIHS, DIHS7)
North America (UL listed, CSA certified)
EN45545-2
IEC 61373
Product Tradename
None
Product Type
Distribution parts
Product Sub Type
None
Public Consumption
Yes
Product Family Description
ES-PMCC-PDC-Eaton Distribution parts
Globally Marketable
Yes
Product Specification Details
Accessory/spare part type
Tripping signal contacts
Additional equipment required
Signaling switch
Admissible back-up fuse - max
6 A gL
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-5 °C
Amperage Rating
2 A
Application
Switchgear for industrial and advanced commercial applications
Assembly width
0.5
Contact function
2 C/O
Conventional thermal current ith of auxiliary contacts (1-pole, open)
2 A
Degree of protection
UL/CSA Type: -
IP40
IP20 (IEC)
Device fitting
Universal
EL number
1609491
Enclosure width
80 mm
Frame
Standard front dimension: 45 mm
Frequency rating
50 Hz / 60 Hz
Functions
Auxiliary switch
Mounting width
8.8 mm (0.5 space units)
Number of contacts (change-over contacts)
2
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0
Number of poles at main contact unit - max
2
Number of switches (fault signal)
0
Rated conditional short-circuit current (Iq) with 6 a back-up fuse
1 kA
Rated impulse withstand voltage (Uimp)
2.5 kV
Rated insulation voltage (Ui)
250 V AC
Rated operational current
2 A (250 V AC-15)
3 A (250 V AC-12)
0.5 A (110 V DC-13)
Rated operational voltage (Ue) - max
250 V
Rated switch current
4 A
Suitable for current of main contact unit - max
4 A
Terminal protection
Busbar tag shroud to BGV A3
Terminal type
Lift terminals
Type
Accessory
Accessory for combined residual current/power circuit breaker
Accessory for miniature circuit breaker
Accessory for residual current circuit breaker
Used with
Trigger signal contact
Accessory
Accessory for combined residual current/power circuit breaker
Accessory for miniature circuit breaker
Accessory for residual current circuit breaker
Voltage rating
230 V AC
Voltage rating per contact - min
5 V DC
Voltage type
AC

Technical data ETIM 9.0

Devices for distribution board-/surface mounting (EG000062) / Auxiliary device for distribution board devices (EC001286)
Electric engineering, automation, process control engineering / Electrical installation, device / Breaker switch component / Auxiliary contact unit for distribution board (ecl@ss13-27-14-35-02 [AKE327018])
Device fitting
Universal
Function
Auxiliary switch
Width in number of modular spacings
0.5
Number of contacts as normally open contact
0
Number of contacts as normally closed contact
0
Number of contacts as change-over contact
2
Number of fault-signal switches
0
Rated switch current
4 A
Rated voltage
250 V
Voltage type
AC
With auto test for earth leakage function
No
Suitable for max. number of poles main contact unit (total)
2
Suitable for max. current main contact unit
4 A