Universal, handy and rugged test instrument for performing all measurements for
testing the effectiveness of safety measures in electrical systems as required by
IEC 60364-6 (DIN VDE 0100-600) and other country-specific standards,
and as specified in the individual sections of DIN EN 61557 (VDE 0413).
[ more... ]
Thanks to its intelligent and ergonomic design, intuitive operation and an advanced
technical concept, the PROFITEST INTRO is aligned consistently to routine daily tasks
making it the ideal companion for any electrician.
The test instrument makes testing in accordance with the following international
standards possible: IEC 60364, DIN VDE 0100, DIN VDE 0105,
DIN EN 61557, CEI 64-8, ÖVE/ÖNORM 8001-6, NIV/NIN,
CSN 33 2000-6, NEN 1010-6, GOST R (ГОСТ
Р) 50571.16-99, IEC 61010
300 V
600 V
Working Efficiently Around the World
- Intuitive operation
- Measuring functions can be selected directly via the rotary switch
- Background illumination
- Help functions with wiring diagrams
- International user interface (12 languages)
- Universal connector system with country-specific measuring adapters for outlets
- Measuring category: CAT III 600V / CAT IV 300V
- Factory calibration certificate included
EASY transfer permits direct incorporation of test instruments from the PROFITEST MASTER range into
DDS-CAD planning software .
- Technical Characteristics
[ more... ]
Measurement of RLO, ZL-PE, ZL-N, RINS, RE, ΔU, rotary field, voltage
- OFFSET management
Ohmic offset values RL-PE, RN-PE and RL-N can be ascertained and subtracted from the measured values for measurement of ZL-PE, ZL-N, RE and ΔU( ZL-N).
- PE detection via finger contact
Measurement of touch voltage via finger contact When a measurement is started and if the ON/START key is touched with a finger, the test instrument detects whether or not dangerous touch voltage is present at the PE terminal relative to ground.
- Low-resistance measurement for protective and equipotential bonding conductors with automatic polarity reversal
- PRO-JUMPER for easy measurement cable compensation
- Highly accurate measurement of internal system and fault loop impedance without tripping the RCD
- Insulation measurement with rising ramp
- Varistor response test with rising ramp and variable test current
- Earthing resistance measurement (loop)
- Voltage drop measurement
Voltage measurement, phase sequence, frequency measurement
- A broad-range measuring device permits use of the test instrument in all alternating and 3-phase electrical systems with voltages from 65 to 500 V and frequencies of 15.4 to 420 Hz.
Testing of RCCB types A, AC, F, B, B+, EV, MI and G/R, as well as SRCDs and PRCDs
- Measurement of touch voltage without tripping the RCCB.
Touch voltage is measured with reference to nominal residual current using ? of the nominal residual current value.
- RCD test with continuously rising ramp, time to trip, tripping current
- Testing RCCBs with: ½×, 1×, 2×, 5× IΔN
- Testing of RCCBs for pulsating residual direct current; testing is conducted with positive or negative half-wave
Communication and software
- ETC software (Electrical Testing Center) for, amongst other functions, creating tree structures and documentation per ZVEH
- Individual measured value memory for approx. 50,000 objects / measured values
- Bidirectional data exchange via USB, DDS-CAD and epINSTROM
- Connection of an RFID reader or a barcode scanner
Type comparison table
PROFITEST |
INTRO |
MBASE+ |
MPRO |
MTECH+ |
MXTRA |
|
|
|
|
|
|
RCD measurements |
|
|
|
|
|
UB measurement without tripping the RCD |
x |
x |
x |
x |
x |
Tripping time measurement |
x |
x |
x |
x |
x |
Tripping current measurement |
x |
x |
x |
x |
x |
Selective, SRCDs, PRCDs, type G/R |
x |
x |
x |
x |
x |
AC/DC sensitive RCDs, types B and B+ |
x |
- |
- |
x |
x |
Testing of insulation monitoring devices (IMDs) |
- |
- |
- |
- |
x |
Testing of residual current monitoring devices (RCMs) |
- |
- |
- |
- |
x |
Testing for N-PE reversal |
x |
x |
x |
x |
x |
Loop impedance ZL-PE / ZL-N |
|
|
|
|
|
Fuse table for systems without RCDs |
x |
x |
x |
x |
x |
Without tripping the RCD, fuse table |
x |
- |
- |
x |
x |
With 15 mA test current without tripping the RCD |
x |
x |
x |
x |
x |
Earth resistance |
|
|
|
|
|
Earth resistance RE (mains operation) I-U measuring method (2/3-wire measuring method via measuring adapter: 2-wire/2-wire + probe), (1 = without probe) |
x(1) |
x |
x |
x |
x |
Earth resistance RE (battery operation) 3 or 4-wire measuring method via PRO-RE adapter |
- |
- |
x |
- |
x |
Soil resistivity ρE (battery operation) (4-wire measuring method via PRO-RE adapter) |
- |
- |
x |
- |
x |
Selective earth resistance RE (mains operation) with 2-pole adapter, probe, earth electrode and current clamp sensor (3-wire measuring method) |
- |
x |
x |
x |
x |
Selective earth resistance RE (battery operation) with probe, earth electrode and current clamp sensor (4-wire measuring method via PRO-RE adapter and current clamp sensor) |
- |
- |
x |
- |
x |
Earth loop resistance ρELOOP (battery operation) with 2 clamps (current clamp sensor direct and current clamp transformer via PRO-RE/2 adapter) |
- |
- |
x |
- |
x |
Equipotential bonding measurement RLO with automatic polarity reversal |
x |
x |
x |
x |
x |
Insulation resistance RINS with variable or rising (ramp) test voltage |
x |
x |
x |
x |
x |
Variable or rising test voltage |
x |
x |
x |
x |
x |
Voltage measurement UL-N / UL-PE / UN-PE / f |
x |
x |
x |
x |
x |
Special measurements |
|
|
|
|
|
Leakage current (clamp measurement) IL, IAMP phase sequence earth leakage resistance RE(INS) voltage drop standing surface insulation ZST meter start-up |
- x x x - - |
x x x x x x |
x x x x x x |
x x x x x x |
x x x x x x |
Leakage current with PRO-AB adapter |
- |
- |
- |
- |
x |
Residual voltage test |
- |
- |
- |
- |
x |
Intelligent ramp |
- |
- |
- |
- |
x |
Features |
|
|
|
|
|
Selectable user interface language |
x |
x |
x |
x |
x |
Memory (database for up to 50,000 objects) |
x |
x |
x |
x |
x |
Test sequence auto-function (programmable) |
- |
x |
x |
x |
x |
RS 232 port for RFID/barcode reader |
x |
x |
x |
x |
x |
USB port for data transmission |
x |
x |
x |
x |
x |
Interface for Bluetooth® |
- |
- |
- |
x |
x |
ETC user software for PC |
x |
x |
x |
x |
x |
Measuring category: CAT III 600 V / CAT IV 300 V |
x |
x |
x |
x |
x |
DAkkS calibration (2 = factory calibration certificate) |
(2) |
x |
x |
x |
x |
Article Number |
M520T |
M520S |
M520N |
M520R |
M520P |
PROFITEST |
INTRO |
MBASE+ |
MPRO |
MTECH+ |
MXTRA |
Video
Notice:
PROFITEST INTRO |
Comment |
|
Firmware ≥ V3.1.0 |
for software IZYTRONIQ
|
|
Firmware < V3.1.0 |
for ETC and other software |
|
|