The METRISO BASE insulation and resistance measuring instruments allow
for quick and effective testing of protective measures in accordance with:
- DIN VDE 0100
- ÖVE-EN 1 (Austria)
- SEV 1000 (Switzerland)
- and regulations specific to other countries as well.
Insulation measurement per EN 61557-2 / VDE 0413 part 2
Low-resistance measurement per EN 61557-4 / VDE 0413 part 4
Voltage testing and measurement up to 500 V
Compact and rugged - for service calls under harsh conditions and laboratory use
-
Digital and analogue display, backlit
- Intelligent filter - precise and measurement-dependent activation
for the measurement of very high resistances
- beating, i. e. compensation of 16 2/3 Hz and 50 Hz interference
- attenuation of capacitive influences from power cables, etc.
- suppression of electric field influences
- Signalling of dangerous contact voltage by means of LED
- Indication of limit value violations by means of LED
- Overvoltage protection - protects the instrument in the event of
inadvertent connection to mains power
- Fuse link for all resistance measuring ranges
- Electronic fuse for protection of the low-resistance measurement RLO also
protects the fuse link in the low-resistance measuring range in the event of
faulty operation
- One measuring point self-test
with test resistance of 10 MΩ per EN 50110 / VDE 0105-100
- Guard terminal for compensating surface current
The insulation measuring instruments are suitable for the following tasks:
- Measurement of insulation resistance at voltage-free devices and systems,
up to 500 V
- Testing of the resistance of earthing conductors, protective conductors
and equipotential bonding
- Checking of test objects for absence of voltage
- Testing of electrostatic discharge capacity at floor coverings (using
shielded measurement cables) - EN 1081
- No. in Metrological Registry of Russian Federation: 73063-18
Type comparison table
|
|
|
|
|
|
METRISO |
XTRA |
TECH |
PRO |
BASE |
INTRO |
Article number |
M550S |
M550P |
M550R |
M550o |
M550N |
Measurements |
|
|
analog |
|
|
PI, DAR Polarization index measurements |
x |
- |
- |
- |
- |
Riso Uvariable =
50 ... 1000 V
(Limit value 1 MΩ) |
x |
- |
- |
- |
- |
Riso URamp =
50 ... 1000 V
Display of breakdown voltage |
x |
- |
- |
- |
- |
Measuring ranges Riso |
10 k ...
...1 TΩ |
10 k ...
200 GΩ |
10 k ...
...1 TΩ |
10 k ...
100 GΩ |
10 k ...
100 GΩ |
Riso U = 50, 100, 250, 500 /
1000 V |
x / x |
x / x |
x / x |
x / - |
(x) / x |
R 10 Ω... 10 kΩ |
x |
x |
- |
x |
x |
RLO 0,01 ... 10
Ω |
x |
x |
x |
x |
- |
U 0 ... 500 /
1000 V |
x / x |
x / x |
x / x |
x / - |
x / - |
Display functions |
|
|
|
|
|
Backlit display |
x |
x |
x |
x |
x |
Limit value LED Limit (green/red)
Additional acoustic signal, limit value per VDE 0100 |
Riso, RLO |
Riso, RLO |
Riso, RLO |
Riso, RLO |
Riso,
- |
LED for dangerous contact voltage (when switched off) |
x |
x |
x |
x |
x |
LCD symbol for external voltage |
x |
x |
x |
x |
x |
Battery level display |
x |
x |
x |
x |
x |
Special functions |
|
|
|
|
|
Data storage in the instrument, 50.000 objects |
x |
- |
- |
- |
- |
Discharge capacitive devices under test |
x |
x |
x |
x |
x |
Safety shutdown (UBatt < 8 V) |
x |
x |
x |
x |
x |
Features |
|
|
|
|
|
Charging socket, RS232 and USB interface |
x |
- |
- |
- |
- |
Measuring categories CAT II 1000V, CAT III 600V |
x |
x |
x |
- |
- |
Measuring category CAT III 600V, CAT IV 300V |
x |
x |
x |
x |
x |
Integrated 10 MΩ test resistor |
x |
x |
x |
x |
- |
DAkkS calibriation certificate in scope of delivery
(W = Proprietary certificate " ) |
x |
x |
(W) |
x |
- |
|