General specifications
Product name
Eaton Moeller series xPole - mRB4/6 RCBO - residual-current circuit breaker with overcurrent protection
Part no.
mRB4-32/3N/C/01-A
EAN
4015081640102
Product Length/Depth
86 millimetre
Product height
75 millimetre
Product width
70 millimetre
Product weight
0.48 kilogram
Compliances
CE Marked
RoHS conform
Certifications
CE
Product Tradename
xPole - mRB4/6
Product Type
RCBO - Residual-current circuit breaker with overcurrent protection
Product Sub Type
None
Delivery program
Application
Switchgear for residential and commercial applications
Product range
mRB4
Basic function
Combined RCD/MCB devices
Number of poles
Three-pole + N
Number of poles (protected)
4
Number of poles (total)
4
Tripping characteristic
C
Release characteristic
C
Rated current
32 A
Fault current rating
0.1 A
Sensitivity type
Type A, pulse-current sensitive
Type
RCBO
Technical Data - Electrical
Voltage type
AC
Voltage rating
230 V
Rated operational voltage (Ue) - max
400 V
Rated insulation voltage (Ui)
500 V
Rated impulse withstand voltage (Uimp)
4 kV
Impulse withstand current
Partly surge-proof, 250 A
Frequency rating
50 Hz
Leakage current type
A
Rated switching capacity
4.5 kA
Rated switching capacity (IEC/EN 60947-2)
4.5 kA
Rated switching capacity (IEC/EN 61009)
4.5 kA
Rated short-circuit breaking capacity (EN 60947-2)
4.5 kA
Rated short-circuit breaking capacity (EN 61009)
4.5 kA
Rated short-circuit breaking capacity (EN 61009-1)
4.5 kA
Rated short-circuit breaking capacity (IEC 60947-2)
4.5 kA
Surge current capacity
0.25 kA
Disconnection characteristic
Undelayed
Tripping
Non-delayed
Back-up fuse
100 Ampere gL
Pollution degree
2
Technical Data - Mechanical
Width in number of modular spacings
4
Device height
80 mm
Built-in depth
70 mm
Mounting style
Tri-stable slide catch - enables removal from existing busbar combination
Degree of protection
IP20
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²
Design verification as per IEC/EN 61439 - technical data
Rated operational current for specified heat dissipation (In)
32 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
15.6 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Additional information
Current limiting class
3
Features
Concurrently switching N-neutral
Standards
IEC/EN 61009

Technical data ETIM 9.0

Circuit breakers and fuses (EG000020) / Earth leakage circuit breaker (EC000905)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / MCB/RCCB combination (ecl@ss13-27-14-22-07 [AFZ810020])
Number of poles (total)
4
Number of protected poles
4
Rated voltage
400 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
32 A
Rated fault current
0.1 A
Leakage current type
A
Current limiting class
3
Power loss
W
Rated short-circuit breaking capacity according to EN 61009
4.5 kA
Rated short-circuit breaking capacity according to IEC 60947-2
4.5 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
4.5 kA
Disconnection characteristic
Undelayed
Surge current capacity
0.25 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
C
Concurrently switching neutral conductor
Yes
With interlocking device
No
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
-25 - 40 °C
Width in number of modular spacings
4
Built-in depth
70 mm
Flush-mounted installation
No
Anti-nuisance tripping version
No
Degree of protection (IP)
IP20
Connectable conductor cross section solid-core
1 - 25 mm²
Connectable conductor cross section multi-wired
1 - 25 mm²