General specifications
Product name
Eaton xComfort Micro/Mini LV systems Final Distribution Boards
Part no.
MICRO-4
EAN
4015081715084
Product Length/Depth
58 millimetre
Product height
125 millimetre
Product width
80 millimetre
Product weight
0.12 kilogram
Compliances
RoHS conform
Certifications
IEC/EN 62208
Product Tradename
xComfort Micro/Mini
Product Type
LV systems
Product Sub Type
Final Distribution Boards
Delivery program
Type
Basic device Installation distribution board MICRO distribution board
Application
Indoor (installation site)
Color
Signal white (RAL 9003)
White
Technical Data - Electrical
Voltage rating at AC
400 V AC
Frequency rating of contacts
50 Hz
Technical Data - Mechanical
Closure type
Other
Enclosure material
Plastic
Width in number of modular spacings
4
Mounting method
Surface mounted (plaster)
DIN-rail
Surface mounting
Material
ABS (plastic)
Degree of protection
IK05 (impact resistance)
IP30
Number of module space units per row
4
Number of rows
1
Terminal type
Without terminals
Built-in depth
70 mm
Built-in height
0 mm
Built-in width
0 mm
Internal depth
53 mm
Cover/door model
With notch
Cover/door type
None
Other
Module rack type
Single-rail
Protective shrouding material
Plastic
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
10 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
12 W
Design verification as per IEC/EN 61439 - technical data
Ambient operating temperature details
-5 °C - 40 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
650 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK05
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP30
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 400 V AC
10.9.3 Impulse withstand voltage
2.8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Additional information
Features
EMC-version
Fitted with:
Basic device
Functions
Basic device
Protection class
II (totally insulated)
RAL-number
9003
Special features
IP30 Protection Class II Plastic housing white (RAL 9003)
Used with
MICRO distribution board
Basic device
Installation distribution board

Technical data ETIM 9.0

Distribution boards (EG000023) / Small distribution board (EC000214)
Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (including small distribution board) / Small distribution board (ecl@ss13-27-14-24-09 [ACN387016])
Mounting method
Surface mounted
Number of rows
1
Width in number of modular spacings
4
Type of covering
None
Cover model
With notch
Type of door
Other
Transparent cover/door
No
Signal passing door
No
With lock
No
Type of closure
Other
Housing material
Plastic
Built-in depth
70 mm
Built-in height
0 mm
Built-in width
0 mm
Inner depth
53 mm
Earthing terminal block
No
Neutral terminal block
No
DIN-rail
Yes
With mounting plate
No
Extension possible
No
EMC-version
Yes
UV resistant
No
Colour
White
RAL-number
9003
Degree of protection (IP)
IP30
Height
125 mm
Width
80 mm
Depth
58 mm